Protection Setting Guidelines

您所在的位置:网站首页 Ir Tr Isd Tsd Protection Setting Guidelines

Protection Setting Guidelines

2024-07-09 08:32:11| 来源: 网络整理| 查看: 265

Protection Setting Guidelines

Presentation

The setting of overcurrent protection relies on installation short-circuit and electrical fault calculations. The setting guidelines cannot replace these calculations.

MasterPact MTZ circuit breakers with MicroLogic X control units offer flexibility to set the required overcurrent protection while maintaining selectivity and stability on transient phenomena, for example, inrush current of transformers or motors, when necessary.

For each circuit, the installation designer needs to provide the following:

oIz: continuous current capacity of the circuit according to IEC 60364-5-52 or national wiring rules. Current carrying capacity is called ampacity in the US National Electrical Code (NFPA 70).

oIfault min: minimum electrical fault current at the end of the circuit depending on earthing system

oTmax short-circuit: maximum time for maximum short-circuit current

Guidelines are given for setting the following protections:

oLong-time overcurrent protection

oShort-time overcurrent protection

oInstantaneous overcurrent protection

oIDMTL overcurrent protection

oDirectional overcurrent protection

Overcurrent Protection Setting Guidelines by Application

The following table gives the guidelines for overcurrent protection setting by application:

Application

MicroLogic 2.0 X

MicroLogic 3.0 X

MicroLogic 5.0 X, 6.0 X, 7.0 X(1)

Secondary side of MV/LV transformer (switchboard main incomer) with other MasterPact, Compact NS, or PowerPact P- and R-frame circuit breaker downstream as feeder

Ir = Iz

tr ≤ 24 s

Isd ≤ Ifault min

Selectivity possible with Compact NSXm and Compact NSX feeders only.

Ir = Iz

tr ≤ 24 s

Ii ≤ Ifault min

Ii tripping mode: Standard

Selectivity possible with PowerPact B-, H-, J-, and L-frame feeders only.

Ir = Iz

tr ≤ 24 s

Isd ≤ Ifault min

tsd  tsd of downstream MasterPact, Compact NS, or PowerPact P- and R-frame circuit breaker(2)

Ii mode: OFF

Secondary side of MV/LV transformer (switchboard main incomer) without other MasterPact, Compact NS, or PowerPact P- and R-frame circuit breaker downstream as feeder

Ir = Iz

tr ≤ 24 s

Isd ≤ Ifault min

Ir = Iz

tr ≤ 24 s

Ii ≤ Ifault min

Ii tripping mode: Standard

Ir = Iz

tr ≤ 24 s

Isd ≤ Ifault min

tsd = 0

Ii mode: ON

Ii tripping mode: Standard

Ii = Isd

Generator output

with other MasterPact, Compact NS, or PowerPact P- and R-frame circuit breaker downstream as feeder

Ir = Iz

tr ≤ 1 s

Isd ≤ Ifault min

Selectivity possible with Compact NSXm and Compact NSX feeders only.

Ir = Iz

tr ≤ 1 s

Ii ≤ Ifault min

Ii tripping mode: Standard

Selectivity possible with PowerPact B-, H-, J-, and L-frame feeders only.

Ir = Iz

tr ≤ 1 s

Isd ≤ Ifault min

tsd > tsd of downstream MasterPact, Compact NS, or PowerPact P- and R-frame circuit breaker(2)

Ii mode: OFF

Generator output

without other MasterPact, Compact NS, or PowerPact P- and R-frame circuit breaker downstream as feeder

Ir = Iz

tr ≤ 1 s

Isd ≤ Ifault min

 

Ir = Iz

tr ≤ 1 s

Ii ≤ Ifault min

Ii tripping mode: Standard

Ir = Iz

tr ≤ 1 s

Isd ≤ Ifault min

tsd = 0

Ii mode: ON

Ii tripping mode: Standard

Ii = Isd

Feeder with other MasterPact, Compact NS, or PowerPact P- and R-frame circuit breaker downstream

Ir = Iz

tr ≤ 16 s

Isd ≤ Ifault min

Selectivity possible with Compact NSXm and Compact NSX feeders only.

Ir = Iz

tr ≤ 16 s

Ii ≤ Ifault min

Ii tripping mode: Standard

Selectivity possible with PowerPact B-, H-, J-, and L-frame feeders only.

Ir = Iz

tr ≤ 16 s

Isd ≤ Ifault min

tsd > tsd of downstream circuit breaker(2)

Ii mode: OFF

Feeder without other MasterPact, Compact NS, or PowerPact P- and R-frame circuit breaker downstream as feeder

Ir = Iz

tr ≤ 16 s

Isd ≤ Ifault min

Ir = Iz

tr ≤ 16 s

Ii ≤ Ifault min

Ii tripping mode: Standard

Ir = Iz

tr ≤ 16 s

Isd ≤ Ifault min

tsd = 0

Ii mode: ON

Ii tripping mode: Standard

Ii = Isd

Power electronic (for example, uninterruptible power supplies, variable speed drives, photovoltaic inverters) with no other circuit breaker downstream

Ir = Iz

tr ≤ 8 s

Isd = 1.5-2 x In≤ Ifault min

Ir = Iz

tr ≤ 8 s

Ii = 2-3 x In≤ Ifault min

Ii tripping mode: Fast

Ir = Iz

tr ≤ 16 s

Isd = 1.5-2 x In≤ Ifault min

tsd = 0

Ii mode: ON

Ii tripping mode: Fast

Ii = 2–3 x In

ERMS settings with ERMS Digital Module only

Ir_ERMS = Iz

tr_ERMS ≤ 1 s

Isd_ERMS = 1.5 x Ir

Ir_ERMS = Iz

tr_ERMS ≤ 1 s

Ii_ERMS = 1.5 x In

Ii_ERMS  tripping mode: Fast

Ir_ERMS = Iz

tr_ERMS ≤ 1 s

Isd_ERMS = 1.5 x Ir

tsd_ERMS = 0

Ii_ERMS = 2 x In

Ii_ERMS  tripping mode: Fast

(1) Ground-fault protection and earth-leakage protection depend on the earthing system and local regulations. As a rule ground-fault and earth-leakage sensitivity should be as low as possible without being disturbed by permanent or transient leakage current. The ground-fault and earth-leakage time delay enables selectivity with downstream devices.

(2) When tsd > 0, a fault clearance time reduction system, such as ZSI or ERMS, is required in the USA by National Electricity Code NFPA 70 (240.87) (2011 edition). Refer to the guidelines for ERMS settings.



【本文地址】

公司简介

联系我们

今日新闻


点击排行

实验室常用的仪器、试剂和
说到实验室常用到的东西,主要就分为仪器、试剂和耗
不用再找了,全球10大实验
01、赛默飞世尔科技(热电)Thermo Fisher Scientif
三代水柜的量产巅峰T-72坦
作者:寞寒最近,西边闹腾挺大,本来小寞以为忙完这
通风柜跟实验室通风系统有
说到通风柜跟实验室通风,不少人都纠结二者到底是不
集消毒杀菌、烘干收纳为一
厨房是家里细菌较多的地方,潮湿的环境、没有完全密
实验室设备之全钢实验台如
全钢实验台是实验室家具中较为重要的家具之一,很多

推荐新闻


图片新闻

实验室药品柜的特性有哪些
实验室药品柜是实验室家具的重要组成部分之一,主要
小学科学实验中有哪些教学
计算机 计算器 一般 打孔器 打气筒 仪器车 显微镜
实验室各种仪器原理动图讲
1.紫外分光光谱UV分析原理:吸收紫外光能量,引起分
高中化学常见仪器及实验装
1、可加热仪器:2、计量仪器:(1)仪器A的名称:量
微生物操作主要设备和器具
今天盘点一下微生物操作主要设备和器具,别嫌我啰嗦
浅谈通风柜使用基本常识
 众所周知,通风柜功能中最主要的就是排气功能。在

专题文章

    CopyRight 2018-2019 实验室设备网 版权所有 win10的实时保护怎么永久关闭